CHAPTER 2 CABLES

2.1       GENERAL


Cables form an important part of any installation but, because they are static, and in normal service are very reliable, they do not always receive the attention that they deserve.
There are three categories of cables associated with industrial installations - power cables, control cables, and special cables for, for example, communications and data transmission circuits.  It is the first two categories which are described in this chapter.  A power cable contains one, two, three or four cores each consisting of a copper conductor surrounded by insulating material; a control cable usually has many cores and is known as a ‘multicore’ cable.  Aluminium is sometimes used as a conductor material; although its conductivity is less than that of copper, it is somewhat cheaper. Corrosion problems, however, preclude its use on some installations, particularly offshore.

2.2       POWER CABLES

Cables are designed for both high-voltage and low-voltage transmission of power.  Though the general construction is similar in both cases, high-voltage cables have thicker insulation and usually have smaller conductors, since low-voltage cables carrying bulk power handle the heavier currents.


2.2.1    General Construction
A power cable is made up of one, two, three or four insulated conductors enclosed in a bedding.  For mechanical protection, wire armouring is wrapped around the bedding, and a coloured outer protective sheath, usually of PVC, is extruded over the armouring, as shown in Figure 2.1.  Each insulated conductor is known as a ‘core’.
FIGURE 2.1
THREE CORE POWER CABLE


2.2.2    Conductors
The size of the copper conductor forming one of the cores of a cable is expressed in square millimetres (mm2), and the current rating of the cable is dependent upon the cross-sectional area of each core.  The very smallest cables have conductors consisting of only one strand of copper; larger cables however have stranded conductors consisting of many individual strands or wires laid up together; this gives flexibility, allowing the cable to be bent more readily during installation.  To achieve a circular conductor, the number of strands follows a particular progression: 3, 7, 19, 37, 61, 127 etc, the diameter of each strand being chosen to achieve the desired cross-sectional area of the whole conductor.
As seen in Figure 2.2, 3-core and 4-core cables in the larger sizes have conductors with the strands laid up in a segmental formation; this achieves a better space factor and reduces the overall diameter of the cable.  It also reduces the inductance of the cable due to decreased spacing between phases.
FIGURE 2.2
SEGMENTAL CORES

Standard conductor sizes range from 1.5mm2 to 400mm2 for 2-core, 3-core and 4-core cables, and from 50mm2 to 1 000mm2 for single-core cables.


2.2.3    Insulation, Covering and Stress Relief
Natural rubber or oil-impregnated paper is no longer used for the insulation of cables up to 3 810/6 600V; synthetic materials are now used.  For high-voltage cables the insulation is ethylene propylene rubber (EPR) and for low-voltage cables it is polyvinyl chloride (PVC).  EPR has good electrical properties and is resistant to heat and chemicals; it is suitable for a conductor temperature up to 85oC.  PVC is a thermoplastic material, therefore care must be taken not to overheat it; it is suitable for conductor temperatures up to 70oC.  PVC insulated cables should not be laid when the temperature is less than 0oC because it becomes brittle and is liable to crack.
High-voltage cables have an earthed metallic screen over the insulation of each core. This screen consists of a lapped copper tape or metallic foil, and its purpose is to control the electric field within the insulation and thus the voltage gradient across it, as shown in Figure 2.3. Also, it avoids any interaction of the electric stresses due to the voltages on different phase conductors within the same cable.
Volts
 
Radius
 
Electric Field Within Insulation
 
Earth Screen
 
Voltage Gradient
 
FIGURE 2.3


VOLTAGE GRADIENT ACROSS HIGH VOLTAGE CABLE INSULATION
Core insulation may be coloured red, yellow, blue and black to identify the three phases and neutral.  Twin cores are coloured red and black.  Single-core cables are identified by coloured PVC tape applied to the outer sheath.

2.2.4    Cable Stress Relief
The copper screen is often terminated in a ‘stress cone’, which may be seen in Figure 2.7.  This is to spread the electric stress which would otherwise tend to concentrate where the screen is cut off at a cable end and could lead to breakdown.  This is further discussed in para. 2.6.4.


2.2.5    Bedding
The bedding consists of a layer of PVC extruded over the core insulation as a base for the armouring.





2.2.6    Armouring
Mechanical protection of the cable is provided by a single layer of wire strands laid over the bedding.  Steel wire is used for 3-core or 4-core cables, but single-core cables have aluminium wire armouring.  With 3-core or 4-core cables the vector sum of the currents in the conductors is zero, and there is virtually no resultant magnetic flux.  This is not so however for a single-core cable, where eddy-current heating would occur if a magnetic material were used for the armouring.  Armouring is described as Steel Wire Armoured (SWA) or Aluminium Wire Armoured (AWA).


2.2.7    Outer Sheath
The outer sheath of extruded PVC protects the armouring and the cable against moisture and generally provides an overall protective covering.
High-voltage cables are identified by outer sheaths coloured red; a black sheath indicates a low-voltage cable (see also para. 2.7).


2.2.8    Selection of Power Cables
The following considerations are taken into account when selecting a power cable for a particular application:

(a)        The System Voltage and Method of Earthing
A low-voltage system usually has a solidly earthed neutral so that the line-to-earth voltage cannot rise higher than (line volts) ¸ √ 3.  However, cables for low-voltage use are insulated for 600V rms core to earth and 1 000V rms core to core
High-voltage cables used in some installations are rated 1 900/3 300V or 3 810/6 600V or 6 600/11 000V, phase/line.  In selecting the voltage grade of cable, the highest voltage to earth must be allowed for.  For example, on a nominal 6.6kV unearthed system, a line conductor can achieve almost 6.6kV to earth under earth-fault conditions.  To withstand this, a cable insulated for 6 600/11 000V must be used.

(b)       The Normal Current of the Cable
The conductors within a cable have resistance, and therefore I2R heating occurs when currents pass through them.  The maximum permissible temperature of the cable depends upon the material of the insulation, and a conductor size must be chosen so that this temperature is not exceeded.  Tables giving the continuous current-carrying capacities of different cables are given in manufacturers’ literature and in the Regulations for the Electrical Equipment of Buildings published by the Institution of Electrical Engineers.
The temperature of a cable depends not only on the rate of heat input due to the passage of load current but also on the rate at which the heat can be carried away.  When using the tables of current ratings it is important to note whether they refer to cables laid in the ground, laid in ducts or laid in air.  De-rating may be necessary if a number of cables are run in close proximity to each other.
Another consideration in selecting a cable is the voltage (IR) drop from the source of supply to the load.  A drop of 1V in a 440V circuit is of little consequence, but it is a significant percentage when the circuit operates at 24V.




(c)        Abnormal Currents in the Cable
One abnormal condition is a sustained overload; a cable must be protected so that an overload cannot persist long enough to cause damage to the insulation by overheating.  For example, for PVC cables laid in air, the overload must not be greater than 1.5 times the continuous maximum rated current and must not persist for longer than four hours.
Another abnormal condition is when a cable has to carry a through short-circuit current.  In this case the temperature of the conductor may be allowed to rise to a higher value, say 150oC, for the short interval between the onset of the fault and its disconnection. The short-circuit current that a given cable can withstand depends upon the speed with which the protection operates.  For example, a PVC cable having conductors of 185mm2 has the following short-circuit ratings:

46kA for 0.2s
20.3kA for 1.0s
11.7kA for 3.0s
The 0.2s rating would be suitable for use with fuse protection, but, where relay-operated circuit-breakers are concerned, a longer time rating would be necessary.  Again, tables of short-circuit ratings are available in manufacturers’ literature.

2.3       CONTROL CABLES

Control cables usually have conductors either 1.50mm2 or 2.50mm2 in cross-section.  The insulation, bedding and outer sheath are of PVC, and they are steel wire armoured.  Multicore cables are available having 2, 3, 4, 7, 12, 19 and 27 cores, each core being identified by a number on the insulation.  The outer sheath of control cables is coloured green.


2.4       MINERAL INSULATED CABLES

Mineral-insulated (Ml) cables are used where the integrity of a circuit is of great importance.  They are particularly resistant to fire and are used in circuits, such as communications or

FIGURE 2.4


MINERAL INSULATED TWO CORE CABLE



emergency lighting, which must continue operational as long as possible after fire has broken out.  They are also very robust and resistant to mechanical damage.
Ml cables are constructed by assembling the single-strand conductor or conductors inside a seamless copper tube.  After threading a number of ‘tablets’ of magnesium oxide insulating material onto the conductors, the whole assembly - conductors, insulation and copper tube -  is drawn down through a series of dies until the magnesium oxide is crushed to a powder and the whole cable is solid.  The final appearance is as in Figure 2.4.
After annealing to make the cable more flexible, an outer sheath of PVC is applied.
Ml cables are available in single-core from 1mm2 to 150mm2, in 2-core, 3-core and 4-core from 1mm2 to 25mm2, and in 7-core from 1mm2 to 4mm2.
Special jointing techniques and materials must be used for terminating MI cables, and great care must be taken to seal the cable ends against the entry of moisture.


2.5       METHOD OF SPECIFYING CABLES

There is a ‘shorthand’ method used to describe the construction of any cable, using abbreviations to indicate the nature of the various materials. For example, a low-voltage cable might be described as:

(Reference)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
Abbreviation
0.6/1kV
STR
CU/
PVC/
PVC/
SWA/
PVC/
HO2/
HCL
3-core, 150mm2

Interpreted this means:
                        1                      0.6kV line to earth
                        2                      1 kV line to line
                        3                      Stranded conductor
                        4                      Copper conductor
                        5                      PVC conductor insulation
                        6                      PVC bedding
                        7                      Steel wire armoured
                        8                      PVC outer sheath
                        9                      see below
                        10                    see below


Another example is:
6.6/11kV
STR
CU/ EPR/ SCR/ PVC/ AWA/ PVC/ HO2/ HCL
1-core, 630mm2
where              EPR indicates ethylene propylene conductor insulation
                        SCR indicates screened
                        AWA indicates aluminium wire armoured.


The last two items (9 and 10) indicate the flammability and the toxicity of the synthetic materials used in the cable.  HO2 indicates that a high level of oxygen is required to sustain combustion: in the case of the specification this means more than 30% oxygen in the atmosphere.  HCL denotes ‘Hydrochloric Level’ showing that, when the synthetic materials burn, they produce hydrochloric acid gas (HCl) which is highly poisonous and very corrosive.

In particular PVC, when burnt, releases large quantities of HCl and also produces dense black smoke; for example, a 1m length of cable containing, say, 6kg of PVC can completely black out a room 1 000m3 in size within five minutes of the fire starting.




2.6       INSTALLATION

 

2.6.1    Cable Runs

Cables may be laid discretely in the ground, run in ducts or clamped to cable trays; the third method is the most common in offshore installations.  Each cable must be identified at each end, using a marker bearing the cable number.
There is a practical limit to the conductor size which can be run as a 3-core or 4-core cable it becomes too stiff and heavy to handle.  A 3-phase circuit is then run as three (or four) single-core cables.  To minimise the electromechanical forces between the cables under short-circuit conditions, and to avoid eddy-current heating in nearby steelwork due to magnetic fields set up by load currents, the three single-core cables comprising the three phases of a 3-phase circuit are always run clamped in ‘Trefoil’ formation, as shown in Figure 2.5.
FIGURE 2.5
SINGLE CORE CABLES LAID IN TREFOIL
At any instant in time the net magnetic flux outside the group of cables due to the three line currents in them approximates to zero because of the symmetrical cable layout.
Heavy current cable runs, such as the low-voltage connections from a transformer, may consist of up to four single-core cables in parallel per phase; all 12 cables are run bunched into four 3-phase sets, each set laid in trefoil.  In the case of 4-wire systems the neutral conductor needs a smaller cross-sectional area than that of the phase conductors and may be met by one or more smaller single-core cables in parallel.

2.6.2    Cable Terminations
A power cable is terminated in an air-insulated cable box in offshore installations; it enters the box through a compression gland which grips the wire armouring and seals the entry of the cable.  The outer sheath, armouring and bedding of the cable are stripped back, enabling the cores to be spread to match up with the fixed bushing terminals, and the insulation is removed to expose the conductors.  Such a cable box is often referred to as a ‘trifurcating box’.
In some high-voltage onshore installations, especially outdoor ones, the cable box may be filled with compound, a tar-like substance which is poured in hot and then sets hard to exclude moisture. It can only be removed by heating.



FIGURE 2.6


LOW VOLTAGE CABLE TERMINATION
Conductors are terminated either with lugs bolted to the fixed bushing stems as shown in Figure 2.6 or, for heavier currents, with cylindrical ferrules which are clamped into terminal blocks. In either case the terminations are crimped onto the conductors using either hand or hydraulic crimping tools. To make a good connection it is vital that the lug or ferrule is the correct size for the particular conductor and that the correct die is used in the crimping tool.
FIGURE 2.7
HIGH VOLTAGE CABLE TERMINATION



Special measures must be adopted, when screened high-voltage cables are terminated, to prevent a concentrated electric field being developed where the copper screening tape is cut back; this strong electric field could lead to the insulation at that point being so overstressed that a breakdown occurs.  Special stress cones are fitted which are bonded to the screening tape; they control the electric stress and reduce the resulting voltage gradients to a safe value.  This arrangement is shown in Figure 2.7.


2.6.3    Single-core Cables
The conductor of a single-core cable and its surrounding metallic armouring act as a current transformer having a 1:1 turns ratio; load current passing through the conductor produces a magnetic flux which, linking with the wires of the armouring, induces an emf in them.  If a circuit is provided between the armouring at one end of the cable and at the other, a current flows in the armouring which, if sufficiently large, causes heating.  This is shown in Figure 2.8(a).
To control these circulating currents insulated cable gland adaptors are used whereby the body of the gland, and consequently the wire armouring of the cable, is electrically isolated from the earthed gland plate of the cable box by a layer of insulation.  Figure 2.8(b) shows a 3-phase circuit run with single-core cables using insulated cable glands.  To control the

FIGURE 2.8


INSULATED CABLE GLANDS



voltage of the armouring it must be bonded to earth; this is done by deliberately bridging the gland insulation using bonding links.  The armouring can be bonded in one of two ways.  In Figure 2.8(a) it is bonded at both ends of the cable run (shown in red); the emf induced in the armouring causes currents (IA) to circulate in the armouring which in heavy current circuits may lead to an undesirable temperature rise in the armouring.  Alternatively, the armouring may be bonded at one end only as in Figure 2.8(b); there is no circuit for current to flow, but a voltage (EA) is developed across the gland insulation at the unbonded end.  Where one end of the circuit is in a hazardous area, it is customary to bond this end so that any arcing that may occur due to emfs induced in the armouring can only take place in the non-hazardous area.
There is one other magnetic problem associated with single-core cables: where such cables enter a cable box or pass through partitions the conductors must pass through holes in the gland plate. If these plates are made of a magnetic material such as steel, the magnetic fields due to the load currents in the conductors induce eddy currents in the gland plate which may cause it to become very hot.  For terminating or passing a.c. circuits using single-core cables, gland plates of non-magnetic material must be used.


2.6.4    Plug-in Connectors
One make of high-voltage, plug-in elbow connector used in some installations is the ‘Elastimold’ type illustrated in Figure 2.9, where the live conducting parts are shown in red.
FIGURE 2.9


ELASTIMOLD HIGH VOLTAGE ELBOW CONNECTOR



If a cable core screen is cut or terminated abruptly, the electric field distribution within the cable changes radically outside it.  Both the surrounding air and the dielectric material immediately in the vicinity of the terminated screen then become overstressed electrically.  The continuity of the earthed cable screen is carried on by the metal elbow past the plug-in connector to the entry bushing on the equipment.  To prevent rapid breakdown of the cable, a stress cone is applied at the end of the screen (bottom of Figure 2.9).  The cone has an insulating portion to reinforce the primary cable insulation and also an earthed conductive portion to mate with the cable core screen.  This is to control the distribution of the equipotential lines (that is, lines of equal voltage) shown in blue, so that, when they finally emerge into the air, they are sufficiently far apart not to cause too great a potential gradient and so not to give rise to ionisation and possible electrical breakdown.
In Figure 2.9 the dispersal of the blue equipotential lines at the cone area (shown as percen­tages of the core voltage) is clearly seen.


2.6.5    Control Cables
Control cables are also terminated using compression glands.  The sheathing and armouring are stripped back to leave tails of the required length.  Each core is identified using plastic ferrules bearing the wire number, and terminated using a crimped connector.  The cores are either laced up into suitable runs using plastic cable ties, or secured to cable racks within a control panel.


2.7       OUTER SHEATH COLOURS

Standard colours are used in some installations to identify the system to which the various cables belong; they are:


Red
:
High-voltage system.
Black
:
Low-voltage system.
Green
:
Control and instrumentation system.
Orange
:
Fire and gas detection and telecommunications systems
Blue
:
Intrinsically safe systems.
Yellow
:
Thermocouple circuits.