This system is also
referred as arc suppression coil grounding. In the previous earthing
methods that we have discussed the earth fault on any one of the phases
caused total shut down of the system. So continuity of supply can be
maintained. This is not he case with ungrounded system whee fault on one
phase will not cause other phases to supply power. This method of
grounding has this advantage of isolated neutral system along with
reduced possibility of arcing grounds and numerous other advantages.
It consists of a coil called Peterson coil or Ground fault neutralizer
or arc supression coil whose function is to make arcing earth faults
self extinguishing and in the case of sustained faults to reduce the
earth current to low value so that system can supply power with one line
earthed.
This
system works on the principle that when inductance and capacitance are
connected in parallel, resonance takes place between them and because of
the characteristics of resonance, the fault current is reduced or can
be neutralized.
The system with fault on phase B is show in the Fig. 1(a). The corresponding phasor diagram is shown in the Fig. 1(b).
Fig. 1 Resonant grounding |
An arc supression coil is an iron-cored reactor similar to oil immersed
transformer connected between neutral of system and earth. This coil is
provided with number of tappings so that it can be tuned with the
capacitance which may vary due to varying operational conditions.
As the system operation is similar to isolated neutral system, the
phase to earth voltage of healthy phase is times the normal phase
voltage and the resultant capacitive current is √3 times the normal
charging current of one phase. The resultant capacitive current will
lead by with faulty phase voltage while the fault current lags by with
faulty phase voltage.
IF = Vph/XL ; IC = 3Vph/XC
The rating of the coil is
continuous and equal to the maximum earth fault current. If a double
phase to ground fault or another ground fault occurs, the current
flowing through the coil is more. This can be prohibited with closing of
a circuit breaker after certain time lag. The earth fault current flows
through the parallel circuit by passing the arc supression coil. Here
the circuit breaker is normally open and closes after the closure of
relay tripping circuit by passing are supression coil.
This method of neutral grounding is used in medium voltage overhead
transmission line which are connected to system generators through
intermediate power transformers. This is because the higher insulation
requirement on the apparatus associated with arc supression coil
grounding system is easily incorporated in power transformers than in
generators. Also the overhead lines are usually subjected to earth
faults due to lightning. Hence protection is required.
No comments:
Post a Comment