In the cases where it is
necessary to limit the fault current then the current limiting element
must be inserted in the neutral and earth. One of the ways of achieving
this is the use of resistance earthing where one or more resistances are
connected between neutral and earth. The resistor may be either of wire
or water column resistances for voltages of 6.6. KV and above. Metallic
resistors do not change with time and requires little maintenance. But
owing to its inductive nature they disadvantages with overhead lines
exposed to lighting as impulses or the travelling waves are subjected to
positive reflection and cause stress on insulation resulting in its
breakdown. Liquid resistors are free from these disadvantages and have
simple and robust construction.
As shown in the Fig. 1(a) let the earth fault occurs on phase B. The
corresponding phasor diagram is shown in the Fig. 1(b). The capacitive
currents and flow through the health lines. The fault current not only
depends on the zero sequence impedance of the source but also on the
resistance in the earth circuit. This fault current can be resolved into
two components one inphase with the fault phase voltage and other
lagging the faulty phase voltage by . This lagging component of current
is in phase opposition to capacitive current and it changes with change
in value of earthing resistance. Thus the value of this resistance is
designed in such a way that during fault on any phase, a current equal
to full load current of largest alternator or transformer flows in earth
resistance which will keep the overvoltages within limits. With fault
current lagging component equal to capacitive current the system
operation is similar to solidly earth system and no transients occur due
to arcing ground.
Fig. 1 |
With
high value of earthing resistance and low value of reactive current
than the capacitive current then system conditions approach to that of
ungrounded system with chances of transient over voltages to occur. The
line to earth voltage of the healthy phases at the time of fault is
little more than line to earth voltage of the solidly grounded system
operating under similar conditions. The duration of this voltage can be
reduced by using suitable protective switchgears to avoid any harmful
effect that may be caused.
The value of resistance to be inserted in earth circuit is given by,
R = VL/√3.I
where VL = Line to Line Voltage
I = Full load current of largest alternator or transformer
The advantages of this system are as follows,
1) The discriminative of type of switchgears may be used for protection.
2) The hazards of arcing grounds are minimzed.
3)
The influence of neighbouring communication circuits is minimized due
to lower value of fault current flowing through earth as compared to
that in case of solidly grounded system.
The disadvantages of this method are given below,
1) As the neutral is shifted during earth faults, the equipments are to be selected for greater voltages.
2) The system is expensive than the solidly grounded system.
3) There is energy loss in neutral grounding resistors for dissipation of fault energy.
This method is normally adopted in system with voltages from 2.2. KV
and 33 KV with a power source capacity more than 5000 KVA.
No comments:
Post a Comment