In this method of earthing,
natural is directly connected to earth by a metallic connection or a
wire of negligible resistance and reactance. The charging currents flows
through the system under normal condition similar to ungrounded system.
Because of the connection of system neutral point to earth, it always
remains at earth potential at all operating conditions and under faulty
conditions voltage of healthy phase will not exceed.
The solid grounding us represented in the Fig. 1.
Fig. 1 Solid earthing |
Whenever there
is earth fault on any one phase (phase B in this case), the phase to
earth voltage of faulty phase is zero while voltage to earth of the
remaining two healthy phases will be normal phase voltages as neutral in
this case is not shifted. The phasor diagram corresponding to this
condition is shown in the Fig. 2.
Fig. 2 Phasor diagram |
Let the capacitive currents flowing in the healthy phases be IR and IY. the resultant capacitive current is vector sum of IR and IY.
The alternator in addition to capacitive current also provides the
fault current. This current flows from fault point through faulty phase
and then return to the alternator through earth and neutral connection.
The resistance of earth fault is negligible. The magnitude of fault
current after the analysis is given by,
This current is
mainly dependent on zero sequence impedance of the source of power and
that of phase conductor upto fault point. As the resistive component of
zero sequence impedance is normally negligible, the fault current which
is large can be assumed as lagging the fault phase voltage by 90o. From the phasor diagram, it can be seen that If and IC are
exactly opposite due to which capacitive current is neutralized by high
fault current which eliminates the possibility of arcing grounds and
overvoltages. The discriminative types of switchgears may be used in
this method.
Followings are disadvantages of this method,
i)
Due to high value pf fault currents, the system may become unstable and
there will be greater interference to neighbouring circuits. Thus this
method is employed where system impedance is sufficiently large to limit
fault current.
ii)
With high values of fault currents, circuit breakers are difficult to
handle and heavy contacts are to be provided in the circuit breakers.
The above disadvantages can be overcome by employing high rupturing
capacity and high speed circuit breakers along with fast operating
relays.
This
method is used in high voltage systems with voltages below 33 kV with
total capacity not exceeding 5000 KVA for the economic reasons.
No comments:
Post a Comment