In this system of earthing,
the neutral point is earthed through a single phase voltage
transformer. The system thus acts as an insulated neutral system. Avery
high reactance earthing is provided due to the voltage transformer.
The connection diagram is shown in the Fig.1.
Fig. 1 |
The voltage
transformer shown in the above figure measures the voltage so that earth
fault on the system is indicated. The travelling waves passing through
the machine winding are reflected through voltage transformer. A surge
divertor is used between neutral and earth to avoid the rise of voltage.
The voltage transformer is used normally in generator circuits which
are directly connected to step up transformers. The generator circuits
are physically isolated from the main distribution system. The
electrostatic capacity of the circuit is negligible as the
interconnecting cables between the generator and transformer windings
are normally short. The risk of overvoltage conditions arising due to
arcing ground is eliminated.