When the transformers or
generators are delta connected or if the neutral points are not
accessible then artificially the neutral earthing point can be created
with the use of star connected earthing transformer. Such transformer
has no secondary. Each phase of primary has two equal parts. There are
three limbs and each limb has two windings providing opposite flux
during normal condition. Such a transformer is shown in the Fig.1.
Fig. 1 |
One set of windings are connected in star providing the neutral point.
The other ends of this set of windings are connected to the second set
of windings as shown in the Fig. 1. The directions of the currents in
the two windings on each limb are opposite to each other. The small
exciting current is circulated in the windings during normal operation.
Under faulty condition, the transformer offers a low impedance path to
the flow of zero phase sequence currents. The value of fault current is
limited in some cases by the use of a resistor in series with the
neutral earthing connection. This is necessary in systems with operating
voltage between 2.2 KV and 3.3 KV.
The transformers are of short time ratings in the range of 10 seconds
to 1 minute. Hence the size of these transformers is small as compared
to power transformers of small rating. If the earthing transformer is
not available then a star-delta transformer is used.
No comments:
Post a Comment