For stable parallel
operation, the most suitable type of d.c. generator is shunt generator
as it has slightly drooping characteristics. If there is any tendency
for a generator to supply more or less than its proper share of load it
changes system voltage which certainly opposes this tendency. This
restores the original division of load. Thus the shunt generators
automatically remains in parallel, once they are paralleled.
If any of the generators is taken out of service then firstly its
field is weakened while the field of other generators is strengthened
till the ammeter associated with that generator reads zero. After this,
the breaker and the concerned switch are opened to take the generator
out of service. This procedure of connecting and disconnecting a
generator from service prevents any shock and sudden disturbance to the
prime mover or the system itself.
If field of any generator is weakened beyond certain extent then
power will be delivered to it. It will then run as a motor in its
original direction. The prime mover associated with it will be thus as a
motor in its original direction. The prime mover associated with it
will be thus driven due to the motoring action of the generator.
Consider voltage-current characteristics of a shunt generator as shown in the Fig. 1(a) and Fig1(b).
Fig. 1 |
Two shunt generators are considered. For common terminal voltage, the two generators are supplying a current of I1 and I2 respectively. It can be seen that generator 2 has more dropping characteristics and supplied less current.
The load will be divided properly within the two generators at
all the points provided their voltage characteristics are similar with
each generator having same voltage drop from no load to full load.
If the two generators are having different kW ratings then they
will share a load in proportion to their ratings with their external
characteristics plotted with reference to percentage of full load
current as shown in the Fig. 2.
Fig. 2 |
If we consider two generators with their ratings as say 5o kW and
100 kW running in parallel and supplying a total load of 120 kW then
generator 1 will supply a total load of 40 kW while the other one will
supply 80 kW.
The combined characteristics of the generators can be obtained
from the individual characteristics of the generators by adding the
currents provided by each generator separately at equal voltage points.
From this resultant characteristics the voltage or the currents provided
by the generators can be obtained. If the generators are having
straight line characteristics then these results can be obtained by
doing the simple calculations instead of plotting graphs.
If the two generators having unequal no-load voltages are sharing a load then its analysis is as given below.
R1 = Armature resistance of generator 1
R2 = Armature resistance of generator2
V = Common terminal voltage
The bus bar voltage can be kept constant and the load can be transferred from generator 1 to 2 by increasing either Φ2 or N2 or by reducing N1 and Φ1 change in N1 and N2 can be achieved by changing the speeds of prime movers while by changing the shunt field rheostats the fluxes Φ1 and Φ2 can be varied.
In summary it should be kept in mind two shunt generators in
parallel having no load voltages equal will share the load in such a
ratio that the load current of each machine produces the same drop in
each generator. If the generators are having unequal no-load voltages
and operated in parallel then the load currents should produce
sufficient voltage drops in each generator so as to keep the terminal
voltage same. The generator having lower voltage drop takes more share
of change in load. If the generators are working in parallel and having
different power ratings but same voltage regulation will divide the load
in proportion to their power ratings.
No comments:
Post a Comment