Consider two compound generators 1 and 2 running in parallel as shown in the Fig. 1.
Fig. 1 |
As the voltage characteristics for the usual compound generators
are rising, their parallel operation is unstable in the absence of
corrective devices.
Let us consider that each generator is taking proper share of
load. If for some reason, the generator 1 takes increased load slightly
then the current passing through its series field winding increases
strengthening its field to increase the generated e.m.f. This causes
generator 1 to take still more load. If system load is assumed to be
constant then the load on generator 2 will decrease weakening its series
field due to less current passing through its field winding which
results in further decrease in its load. This effect is cumulative which
leads generator 1 to take the entire load and generator 2 will be
driven as motor. The circuit breakers of at least one of the two
generators will open to stop the parallel operation. The under compound
generators show stable operation like shunt generators.
For stable parallel operation of over and level compound
generators, equalizer bus bars are used. It is connected to the armature
ends of the series coils of the generators. The equalizer bus bar is
also a conductor which is not required is case of under compound
generator as their characteristics are not rising.
Now consider that the same two compound generators are operating
in parallel with equalizer bar between them. If for any reason,
generator 1 starts taking more load than its proper share the its series
field current is increased. But now this increased field current will
partly pass through series field winding of generator 1 and partly
through series field winding of generator 2 via equalizer bar. Thus the
two generators are affected in similar way preventing generator 1 from
taking extra load. To have proper division of load from no load to full
load it is required that the regulation of each generator must be same.
The series field resistances should be inversely proportional to the
generator ratings.
No comments:
Post a Comment