The low ground resistance in
case of high voltage substations can be obtained with the use of
interconnected ground grids. In a typical grounding grid system, a
number of interconnected bare soild copper conductors are buried at a
depth of 0.3 to 0.6 m and spaced in a grid pattern. It provides common
earth for all devices and metallic structures in the substation.
At each of the junction point, the conductors are bonded together. This
system is usually suported by a number of vertical rods about 3 m long
at some joints.
If a is cross-sectional area of copper, in circular miles, t is the fault duration in seconds, Tm is the maximum allowable temperature and Ta is the ambient temperature then the size of grid conductors required which prevents fusing under the fault current is given as,
If the grid depth is less than 0.25 m then the earthing resistance of the grid is given by,
Here R = Grid resistance in ohms
a = Ground area occupied by grid in m2
L = Total length of buried conductors in m
But when the grid depth is greater than 0.25 m then earthing resistance is given by,
The effective grounding of the equipment is possible through the grid.
Also the voltage gradient at the surface of the earth can be controlled
at safe value for human contacts with the addition of ground rods, the
ground resistance further reduces when soil resistivity in the upper
layer is more than the soil underneath.
No comments:
Post a Comment