The most important factor in
the substation is the grounding. The system neutral is connected to the
ground through grounding. The discharge path for surge arrestors and
safety of operating personnels can also be achieved through grounding
The grounding gives low resistance path to earth and reduces rise in
ground potential which is dependent on magnitude of fault current and
resistance of grounding system. The low resistance of substation ground
can not be obtained in deserts and rocky areas.
The convenient way for getting proper ground connection is through
grids. If the ground rods are used in addition then it reduces the
ground resistance. Depending on the size of the substation, nature of
soil and the grounding resistance required, the size of grid and number
along with length of driven rods can be determined.
Under the fault condition, the potential of earth and its gradient over
the surface out from the electrode is dependent on the ground
resistance. The systems with higher values for maximum ground fault
current, it is not possible to have lower values for ground resistance
so as to have rise in grounding system potential to safe value.
The practical solution for grounding at substation yards is through
grid or mat. The grid consists of a number of meshes and connected to
several earth electrodes driven at intervals.
The total number of electrodes required is determined by using the expression.
Number of electrodes = Maximum Fault Current/ 500
The grounding resistance for a grounding grid or mat is calculated from the following expression,
Here ρs is resistivity of soil in Ω-m, L is total length of buried conductor in meters and r is radius of circular plate in meters.
The size of grounding conductor should be appropriate so as to have
thermal stability for ground fault current and it should be mechanically
strong. The minimum cross section for the grounding conductor having
required thermal stability is determined from the following expression,
Where IF
is fault current in amperes while t is time in seconds for the
operation of protective relays including circuit breaker tripping time. C
is a constant. Its value is 70 for steel having temperature rise of 400oC while for copper with temperature rise of 300oC, its value is 165.
The minimum size required for proper mechanical strength in case of steel is 61 mm2. for copper it is 107.2 mm2 while in case of aluminium it is 195 mm2.
In case of grounding conductors made up of steel, its size should be
checked for corrosion. If the soil is moderately or severely corrosive
then the steel strip of minimum thickness 6 mm and minimum cross section
area should be 200 mm2.
The earthing grid system is normally extended over the total substation
yard and in few cases, several meters beyond it. The grounding
conductors should have low impedance. They should be able to carry
prospetcive fault current without getting fused or damaged. They must
take account the future expansion of connected power system.
No comments:
Post a Comment