Insulation Resistance to Earth (Low Voltage Generators 100 – 690VAC) - LEKULE

Breaking

14 Feb 2016

Insulation Resistance to Earth (Low Voltage Generators 100 – 690VAC)

Insulation Resistance to Earth
Low Voltage Generators 100 – 690VAC.
Note
When conducting high voltage test to earth, it is advisable to
either disconnect or short out any electronic devices, such as the
Automatic Voltage Regulator, (AVR), and Main rotor diodes.
Short circuiting the terminals can be achieved with a piece of fuse
wire, which must be removed immediately after the tests are
completed.
Caution: Running the Generator before removing the short circuit
connection could seriously damage the Generator.
When Megger testing a machine, failure to protect the voltage
control unit and diodes could result in permanent damage to one
or more of the electronic components.
The resistance of the insulation between the copper conductors
and the frame of the machine, (earth or ground), is measured by
means of a high voltage tester, or "Megger", which applies a D.C.
potential of 500 or 1000 volts across the winding insulation.

The high voltage causes a current to ‘leak’ through the insulation
system. This current produces an output reading on the Insulation
tester (‘Megger’), which is measured in Megohms (resistance to
earth or ground). A normal value for a low voltage Generator
winding should be higher than 1 Megohm to earth.
Generators with an output voltage of between 100V to 600V
should be tested as above. If the output winding (stator) is lower
than 1 Megohm to earth, the windings should be cleaned, dried,
or removed to a workshop for complete refurbish. 

No comments: