In Article " Electrical Boxes - Part One
", I explained that there are many types of Electrical boxes used in a
conduit installation. The application and site conditions determine the
type of box used. The electrical boxes can be divided to:
And I explained the first type: the outlet boxes in this Article.
Today, I will explain other types of Electrical Boxes as follows.
You can review the following articles in the same course for more information:
- The outlet boxes,
- Device boxes,
- Pull and junction boxes.
And I explained the first type: the outlet boxes in this Article.
Today, I will explain other types of Electrical Boxes as follows.
You can review the following articles in the same course for more information:
Second:
Device Boxes
|
Third: Junction and pull boxes
1- Metal
surface-mounted pull boxes
They finished
with gray enamel paint are available with or without knockouts. Widths and
heights are from 4 to 24 in., and depths are from 4 to 8 in. These boxes
include covers attached with screws.
2- Galvanized
metal surface-mounted pull boxes
They are
available with or without knockouts. Widths and heights are from 4 to 36 in.,
and depths are from 4 to 12 in. These boxes also include covers attached with
screws.
3- Metal
junction pull boxes with hinged covers
They finished
in gray enamel, are also available with or without knockouts Widths are from
41_2 to 24 in., heights are from 5 to 12 in., and depths are from 3 to 6 in.
4-
Moisture-proof, gasketed boxes with metal screw-on covers
They finished
in gray enamel, do not have knockouts. Widths and heights are from 6 to 12
in., and depths are from 4 to 6 in.
5- Double-door
metal transformer cabinets
They finished
in gray enamel, do not have knockouts. Widths are 36 in., heights are 30 to
36 in., and depths are 10 in.
|
Sizing of Junction and pull boxes according to NEC Section 314-28
The size of the
box is based on the size and number of conductors, as well as the number of
raceways and their diameter As per
Section 314-28(a) which applies for 3/4 inch or larger raceways (conduit or
cable) with #4 or larger conductors or cables pulled through the raceway.
1- For a
Straight Pull
The width of a
box for a straight pull is determined by the size of the largest conduit and
by the space required by the locknuts and bushings. The length cannot be less
than eight times the largest conduit. This rule applies to raceways 3/4 inch
or larger with conductors #4 or larger.
For
example, trade size 2 conduit containing four 4/0 AWG, Type THHW conductors
requires (8 x
2
in. = 16 in. long pull box).
However,
although 16 in. is the required minimum length, a longer pull box may be
desired for maximum ease in handling this size conductor.
2- For Angle
Pull, or U-Pull, or Splices
In an angle pull, or
U-pull, a group of conduits enters a pull or junction box at one side and
leaves at the top or bottom. When the minimum length is figured from the
rules of 314-28(a)(2), this length sets the minimum width also. The inside
length of the box must not be less than six times the largest raceway plus
the sum of the diameters of all additional raceways entering the box. The
wall, or row, with the most conduit entries must be used to size the junction
box.
The diagonal
distance between the centers of the raceways where they enter the box must be
six times the raceway’s diameter.
Adjusting
the previous example of trade size 2 conduit containing four 4/0 AWG, Type
THHW conductors, provided the conductors were spliced within the enclosure,
the required pull box dimension could be reduced to a 12-in.-long pull box (6
x
2
in. = 12 in.).
Another example
for sizing of U Pull box is illustrated in the below image.
Special case:
If the
raceway enclosing the same conductor, the raceway are required to have a
minimum separation between them. The intent is to provide adequate space for
the conductor to make the bend.
For example,
the calculations for raceway having the same conductor are made in below
image.
|
No comments:
Post a Comment