The large alternating
currents which can not be sensed or passed through normal ammeters and
current coils of wattmeters, energymeters can easily be measured by use
of current transformers along with normal low range instruments.
A transformer is a device which consists of two windings called
primary and secondary. It transfers energy from one side to another with
suitable change in the level of current or voltage. A current
transformer basically has a primary coil of one or more turns of heavy
cross-sectional area. In some, the bar carrying high current may act as a
primary. This is connected in series with the line carrying high
current.
The secondary of the transformer is made up of a large number of
turns of fine wire having small cross-sectional area. This is usually
rated for 5 A. This is connected to the coil of normal range ammeter.
Symbolic representation of a current transformer is as shown in the Fig.
1.
Fig. 1 Current transformer |
1.1 Working Principle
These transformers are basically step up transformers i.e.
stepping up a voltage from primary to secondary. Thus the current
reduces from primary to secondary. So from current point of view, these
are step down transformers, stepping down the current value considerably
from primary to secondary.
Let N1 = Number of turns of primary
N2 = Number of turns of seconadry
I1 = Primary current
I2 = Secondary current
For a transformer,
I1/I2 = N2 /N1
I1/I2 = N2 /N1
As N2 is very high compared to N1, the ratio I1 to I2
is also very high for current transformers. Such a current ratio is
indicated for representing the range of current transformer. For
example, consider a 500 : 5 range then it indicates that C.T. Steps down
the current from primary to secondary by a ratio 500 to 5.
... I1/I2 = 500/2
... I1/I2 = 500/2
Knowing this current ratio and the meter reading on the
secondary, the actual high line current flowing through the primary can
be obtained.
Example 1 : A 250 : 5, current transformer is used along with an ammeter. If ammeter reading is 2.7 A,. estimate the line current.
Solution : I1/I2 = 250/5
But as ammeter is in secondary, I2 = 2.7 A
... I1/2.7 = 250/5
... I1 = 135 A
So line current is 135 A.
Solution : I1/I2 = 250/5
But as ammeter is in secondary, I2 = 2.7 A
... I1/2.7 = 250/5
... I1 = 135 A
So line current is 135 A.
1.2 Construction of Current Transformer
There are two types of construction used for the current transformers which are,1. Wound type 2. Bar type
1.2.1 Wound Type Current Transformer
In wound type construction, the primary is wound for more than
one full turn, on the core. The construction is shown in the Fig. 2.
Fig. 2 Wound type current transformer |
In a low voltage wound type current transformer, the secondary
winding is wound on a backelite former. The heavy primary winding is
directly wound on the top of the secondary winding with a suitable
insulation in between the two. Otherwise the primary is wound completely
separately and then tapped with suitable insulating material and
assembled with the secondary on the core.
The current transformers can be ring type or window type. Some
commonly used shapes for the stampings of window type current
transformers are shown in the Fig. 3.
Fig. 3 Stampings for current transformers |
The core material for wound type is nickel-iron alloy or an
oriented electrical steel. Before installing the secondary winding on
core it is insulated with the help of end collars and circumferential
wraps of pressboards. Such pressboards provide additional insulation and
protection to the winding from damage due to the sharp corners.
1.2.2 Bar Type Current Transformer
In this type of current transformer, the primary winding is
nothing but a bar of suitable size. The construction is shown in the
Fig. 4.
Fig.4 Bar type current transformer |
The insulation on the bar types primary is bakelized paper tube
or resin directly moulded on the bar. Such bar type primary is the
integral part of the current transformer. The core and the secondary
windings are same in bar type transformer.
The stampings used for the laminations in current transformers
must have high cross-sectional area than the ordinary transformers. Due
to this, the reluctance of the interleaved corners remains as low as
possible. Hence the corresponding magnetizing current is also small. The
windings are placed very close to each other so as to reduce the
leakage reactance. To avoid the corona effcet, in bar type transformer,
the external diameter of the tube is kept large.
The windings are so designed that without damage, they can
withstand short circuit forces which may caused due to short circuit in
the circuit in which the current transformer is inseted.
For small line voltages, the tap and varnish are used for
insulation. For line voltages above 7 kV the oil immersed or compound
filled current transformers are used.
1.3 Why Secondary of C.T. Should not be Open ?
It is very important that the secondary of C.T. should not be
kept open. Either it should be shorted or must be connected in series
with a low resistance coil such as current coils of wattmeter, coil of
ammeter etc. If it is left open, then current through secondary becomes
zero hence the ampere turns produced by secondary which generally oppose
primary ampere turns becomes zero. As there is no counter m.m.f.,
unopposed primary m.m.f. (ampere turns) produce high flux in the core.
This produces excessive core losses, heating the core beyond limits.
Similarly heavy e.m.fs will be induced on the primary and secondary
side. This may damage the insulation of the winding. This is danger from
the operator point of view as well. It is usual to ground the C.T. on
the secondary side to avoid a danger of sock to the operator.
Hence never open the secondary winding circuit of a current transformer while its primary winding is energised.
Thus most of the current transformers have a short circuit link
or a switch at secondary terminals. When the primary is to be energised,
the short circuit link must be closed so that there is no danger of ope
circuit secondary.