Over Current and Earth Fault Protection of Transformer
Backup protection of electrical transformer is simple Over Current and Earth Fault protection applied against external short circuit and excessive over loads. These over current
and earth Fault relays may be of Inverse Definite Minimum Time (IDMT)
or Definite Time type relays. Generally IDMT relays are connected to the
in-feed side of the transformer.
The over current
relays can not distinguish between external short circuit, over load
and internal faults of the transformer. For any of the above fault, backup protection i.e. over current and earth fault protection
connected to in-feed side of the transformer will operate. Backup
protection is although generally installed at in feed side of the
transformer, but it should trip both the primary and secondary circuit
breakers of the transformer.
Backup protection of transformer has four elements, three over current relays connected each in each phase and one earth fault relay connected to the common point of three over current relays as shown in the figure. The normal range of current settings available on IDMT over current relays is 50% to 200% and on earth fault relay 20 to 80%.
Another range of setting on earth fault relay is also available and may be selected where the earth fault current is restricted due to insertion of impedance in the neutral grounding. In the case of transformer winding with neutral earthed, unrestricted earth fault protection is obtained by connecting an ordinary earth fault relay across a neutral current transformer. The unrestricted over current and earth fault relays should have proper time lag to co - ordinate with the protective relays of other circuit to avoid indiscriminate tripping.